GDSF-311WPD 3-In-1 SF6 Gas Analyzer

GDSF-311WPD 3-In-1 SF6 Gas Analyzer

Brief Description:

GDSF-311WPD (GDSF-411WPD) is an ideal instrument when it is necessary to test water content, purity and decomposition products of SF6 gas. The core component of dew point test is DRYCAP®  series sensors produced by Finland Vaisala company. 


Product Detail

Product Tags

GDSF-311WPD 3-In-1 SF6 Gas Analyzer
General Information

GDSF-311WPD (GDSF-411WPD) is an ideal instrument when it is necessary to test water content, purity and decomposition products of SF6 gas. The core component of dew point test is DRYCAP®  series sensors produced by Finland Vaisala company. The infrared principle SF6 gas purity testing sensor manufactured by European Sensor Company is used to test the purity of SF6 gas. The electrochemical sensor manufactured by Mombabo Company in Switzerland is used as the sensing element for the test of SF6 gas decomposition products. With professional hardware chips and excellent software algorithms of STMicroelectronics, we have produced a new generation of 3-in-1 gas analyzer.

Application

GDSF-311WPD-3-in-1-SF6-Gas-Analyzer-application3

Features

GDSF-311WPD 3-in-1 SF6 Gas Analyzer application4

Specification

SF6 Humidity
Measurement method: Resistive and Capacitive measurement principle
Measurement range: dew point -80℃--+20℃(support ppmv)
Accuracy: ±1℃
(when the dew point temperature is below 0 ℃, the sensor output is the frost point)
Response time: 63% [90%]
+20→-20℃ Td 5s[45s]
-20→-60℃ Td 10s[240s]
Resolution: 0.01℃
Repeatability:    ± 0.5 ℃
Display unit: ℃, ppm, ℃P20(converted value at 20℃)
Gas flow: 400-600ml/min
Flow display: 0-1000mL digital flow meter
Sample gas pressure: ≤1MPa

SF6 Purity
Measurement method: Infrared Measurement Principle (NDIR series sensors)
Measuring range: 0 ~ 100% SF6
Response time: [90%] 60s
Accuracy: ± 0.5%FS
Repeatability: ± 0.5%
Resolution: 0.01%
Display unit: %

SF6 Decomposition Products
Measurement method: Electrochemical Measurements Principle (Electrochemical series sensors)
Measurement range: H2S: 0 ~ 200ppmv
SO2: 0 ~ 200ppmv
CO: 0 ~ 500ppmv
HF: 0 ~ 50ppmv
Accuracy: H2S: 10ppmv ±3%
SO2: 10ppmv ±3%
CO: 50ppmv ±4%
HF: 10ppmv ±3%
Repeatability: H2S: 10ppmv ±2%
SO2: 10ppmv ±2%
CO: 50ppmv ±2%
HF: 10ppmv ±2%
Resolution: 0.01ppmv
Display unit: ppmv
Power supply: 220VAC±10%, 50Hz, AC/DC use, over-charge protection, continuous working is no lower than 8hours.
Use environment temperature: -20--+60℃
Environment humidity: 90%RH
Measurement value influence: No effect of pressure and flow
Dimension: 395*295*155mm
Weight: about 2kg.

GDSF-411WPD SF6 Decomposition Products
 Accuracy: H2S: <10ppmv ±0.3ppmv; >10ppmv ±3%
SO2: <10ppmv ±0.3PPmv; >10ppmv ±3%
 Repeatability: H2S: <10ppmv ±0.2ppmv; >10ppmv ±2%
SO2: <10ppmv ±0.2PPmv; >10ppmv ±2%
 Recycling and filling function: recycling chamber 2L, recycling time ≤ 5min
With gas drying function
● Dimension: 395*295*315mm
● Weight: about 5kg.

Accessories
Main Tester 1 piece
Adapter 1 set
Teflon pipe(include flow adjustment valve and fast connector) 1 set
Tail pipe 1 set
Spare parts 1 set
Charger 1 piece
Users Guide 1 piece
Test Report 1 piece

  • Previous:
  • Next:

  • Send your message to us:

    Write your message here and send it to us

    Send your message to us:

    Write your message here and send it to us